03 / AN ILLUSTRATIVE STARTING POINT
A selected new-installation support duty
Power in kW and stored energy in kWh are different specifications. Both need to be checked.
20 kWSelected running load
1 hIllustrative duration
~24.7 kWhNominal energy before margins
20 kW × 1 h ÷ (0.90 × 0.90)
A hypothetical 20 kW essential-load group for one hour.
Civil suitability and commissioning readiness are not established by the energy example.
Assumes 90% usable battery energy and 90% conversion efficiency for explanation only. Actual output, usable capacity, ageing, temperature, reserve and surge requirements change the design. This is not a quoted package or a backup guarantee.
Reference: EIA explanation of power and energy capacity ↗