03 / AN ILLUSTRATIVE STARTING POINT
Illustrative office and selected test-support loads
Power in kW and stored energy in kWh are different specifications. Both need to be checked.
8 kWSelected running load
1 hIllustrative duration
~9.9 kWhNominal energy before margins
8 kW × 1 h ÷ (0.90 × 0.90)
A defined 8 kW essential-load group for one hour.
Precision testing requirements, HVAC and motor starts need separate verification.
Assumes 90% usable battery energy and 90% conversion efficiency for explanation only. Actual output, usable capacity, ageing, temperature, reserve and surge requirements change the design. This is not a quoted package or a backup guarantee.
Reference: EIA explanation of power and energy capacity ↗