03 / AN ILLUSTRATIVE STARTING POINT
Selected institutional and communication loads
Power in kW and stored energy in kWh are different specifications. Both need to be checked.
5 kWSelected running load
2.5 hIllustrative duration
~15.4 kWhNominal energy before margins
5 kW × 2.5 h ÷ (0.90 × 0.90)
An illustrative 5 kW essential group over two and a half hours.
Network availability and future load changes are outside the calculation.
Assumes 90% usable battery energy and 90% conversion efficiency for explanation only. Actual output, usable capacity, ageing, temperature, reserve and surge requirements change the design. This is not a quoted package or a backup guarantee.
Reference: EIA explanation of power and energy capacity ↗