03 / AN ILLUSTRATIVE STARTING POINT
Steady workshop-support demand after starting
Power in kW and stored energy in kWh are different specifications. Both need to be checked.
11 kWSelected running load
1.5 hIllustrative duration
~20.4 kWhNominal energy before margins
11 kW × 1.5 h ÷ (0.90 × 0.90)
An illustrative 11 kW running load for 90 minutes.
Starting peaks are outside this energy example and need independent verification.
Assumes 90% usable battery energy and 90% conversion efficiency for explanation only. Actual output, usable capacity, ageing, temperature, reserve and surge requirements change the design. This is not a quoted package or a backup guarantee.
Reference: EIA explanation of power and energy capacity ↗