03 / AN ILLUSTRATIVE STARTING POINT
A defined essential and selected-cooling group
Power in kW and stored energy in kWh are different specifications. Both need to be checked.
9 kWSelected running load
1.25 hIllustrative duration
~13.9 kWhNominal energy before margins
9 kW × 1.25 h ÷ (0.90 × 0.90)
A hypothetical 9 kW average supported load for 75 minutes.
Temperature guarantees and compressor starts need their own verification.
Assumes 90% usable battery energy and 90% conversion efficiency for explanation only. Actual output, usable capacity, ageing, temperature, reserve and surge requirements change the design. This is not a quoted package or a backup guarantee.
Reference: EIA explanation of power and energy capacity ↗