03 / AN ILLUSTRATIVE STARTING POINT
A defined site-services backup group
Power in kW and stored energy in kWh are different specifications. Both need to be checked.
8 kWSelected running load
1.5 hIllustrative duration
~14.8 kWhNominal energy before margins
8 kW × 1.5 h ÷ (0.90 × 0.90)
A hypothetical 8 kW selected service load for 90 minutes.
This example does not establish service response time or staff maintenance authority.
Assumes 90% usable battery energy and 90% conversion efficiency for explanation only. Actual output, usable capacity, ageing, temperature, reserve and surge requirements change the design. This is not a quoted package or a backup guarantee.
Reference: EIA explanation of power and energy capacity ↗