Power in kW and stored energy in kWh are different specifications. Both need to be checked.
6 kWSelected running load
2 hIllustrative duration
~14.8 kWhNominal energy before margins
6 kW × 2 h ÷ (0.90 × 0.90)
A hypothetical 6 kW common-services running load for two hours.
Lifts, pumps and individual premises are outside this example.
Assumes 90% usable battery energy and 90% conversion efficiency for explanation only. Actual output, usable capacity, ageing, temperature, reserve and surge requirements change the design. This is not a quoted package or a backup guarantee.